Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T05CM05727
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2006 | FRAMING | Approved | IVRS - Inspection :* 1) ITEM 03050 NOT APPLICABLE PER PAPERWORK TURNED IN BY J. RIVA |
|
02/22/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
02/21/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FIRE BLOCK W/H PLENIUM 2) FIRE BLOCK DEN ARCH WALL CHASE 3) SHIM HEADERS WHERE NEEDED 4) DBL TOP PLATE LIVING ROOM NORTH WALL DBL TOP PLATES WITHIN 24" SPLICE 5) NO WATER TEST DWV SYSTEM PEX OK 6) PROVIDE ENGINEERING FOR OSB TRUSS GUSSET PLATES IN HALLWAY 7) BATH 4" FLEX RESTRICTED 8) RAISE WINDOW MASTER BATH 9) OVER SPAN BEDROOM CLOSET MASTER 10) 1 1/2" VTR MISSING AT BATH 11) STOPPED INSPECTION |