Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T05CM05722
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/02/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
12/01/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SERVICE DICONN ONLY JUMPERED WITH # 12 INSUFFICIENT ALSO CANNOT DOUBLE LUG SEE SECTION 250-32 D 2002 NEC 1411 N 3RD- AS PER LAST INSPECTION-GROUND WIRE FROM RODS TO BE TIED TO NEUTRAL ALSO NO DOUBLE LUGGING ON GROUND TERMINAL IN DISCONNECT JUMPER IS TO SMALL SEE SECTION 250-32 D 2002 NEC |
|
11/30/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*#4 GROUND WIRES BELOW SERVICES AND TO RUN GOING INTO GUTTER. AT BOTH SEPARATE UNITS, THE MAIN DISCONNECTS HAVE TO HAVE THE GROUND WIRE FROM RODS TIED TO NEUTRALS TO INSIDE OF UNITS SINCE AN EQUIPMENT GROUND WAS NOT BROUDHT FROM SERVICE. CAREFUL NOT TO MULT???TERMINALS |
|
11/29/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :*CALL WHEN READY 1415,1411,1409 | |
11/23/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :*RECALL AND GIVE NAME ( NEED ONE) |