Permit: T05CM05720

Parcel: 13316039A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05CM05720

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
03/01/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
1. NSF LISTING ACCEPTED
2. LETTER FROM OWNER DELETING SODA AND JUICE DISP. ACCEPTED.
3. NEED TO SUPPORT INDIRECT DRAIN FOR H.1
4. BACKFLOW CERTS RECEIVED
02/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. RATIONAL EQUIP NEEDS UPC OR CSA LISTING FOR BACKFLOW CONDITIONS.
2. NEED IRRIGATION CERT
3. WILL COLLECT ALL BACKFLOW CERTS AT LATER INSP.
4. PROVIDE MIN 1" AG ON INDIRECT DRAINS
5. PVC INDIRECT DRAINS REQUIRE PRIMER & SUPPORT
02/15/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PROVIDE LISTING FOR BACKFLOW PROTECTION FOR RATIONAL COMB OVEN OR INSTALL BACKFLOW PROTECTION .
PROVIDE BACKFLOW CERTS FOR ALL INTERNAL ASSEMBLIES INCLUDING IRRIGATION
ALL EQUIPMENT SHALL BE INSTALLED FOR FINAL.
01/02/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
NO PROBLEM W/TEMP C OF O FROM PLUMBING INSPECTOR IN ALL AREAS EXCEPT KIT
12/26/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
OK TO COVER WALLS IN KIT.
12/22/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
AS OF DEC. 20 - 06
THERE IS GALV PIPING UPSTREAM OF IRRIGATION BACKFLOW ASSEMBLY. CERTIFICATION SHALL BE DATED AFTER CORRECTING INSTALLATION.

PIPING INSULATION SHALL BE SEALED W/ADHESIVE PER SPEC#25 AND MANUFACTURES INSTALLATION REQUIREMENTS.

PROVIDE LETTER FROM ENGINEER FOR PIPE CHANGE
AT ICE MAKER

DOES P-9 CONNECT TO 3/4 OR 1/2"?
12/20/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
INTERMEDIATE INSPECTION OF REVISED KIT AREA
WATER PIPING NOT PER PLAN
140 DEG. NOT SHOWN TO OVER
3/4" PIPE SPECIFIED TO EQUIPT. AT OVEN, DISHWASHER AND ICE MAKER
OK TO INSULATE AFTER CORRECTING DWV OK
11/16/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- REGULATE MIXING VALVE TO DELIVER NO MORE
THAN 120 DEGREES.
- EVERYTHING ELSE EXCEPT KIT AND IRRIGATION SUPPLY
IS OK.
- CALL FOR 03040 INSP. WHEN BACKFLOW PREVENTION DEVICE HAS BEEN INSTALLED AND CERTIFIED.
- USE NON-FERROUS PIPING UPSTREAM OF ASSEMBLY.
11/13/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
SEE NOTES FROM 10/25
1. PROPER USE OF FITTING REQUIRED AT CLEAN OUT PLUGS.
2. PUBLIC USE LAVS REQUIRE TEMPERED WATER
3. IRRIGATION BACKFLOW DEVICE NOT YET INSTALLED,
NOTE: IRRIGATION PIPING HAS NOT BEEN INSTALLED
4. CLEAN OUT MISSING AT BREAKROOM SINK.
5. TRAFFIC RATED C.O COVER NEEDED AT SEWER
6. INSTALL WC CHINA BOWL CAPS.
7. INSTALL HB VAC BREAKERS

ROOF OK
KIT. AREA NOT COMPLETE
WATER HEATER AND SAFETY DEVICES OK
TOILET ROOMS OPERABLE
I SEE NOT PROBLEMS THAT WOULD PREVENT TCO OTHER THAN HB VAC BREAKERS AND LAV TEMPERING VALVES.
10/25/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- USE FACTORY TAPPED CLEANOUT PLUGS IF USING PLUG TO SECURE COVER.
- TEMPERATURE LIMITING DEVICES REQUIRED AT PUBLIC USE LAVS.
- ROUGH PLUMBING IN REVISED KIT AREA OK TO COVER
PROTECT PIPING PASSING THRU CONCRETE.