Permit: T05CM05720

Parcel: 13316039A

Inspection Status: Approved

Inspection History: PLUMBING - ROOF DRAINS

Permit Number - T05CM05720

Inspection Description - PLUMBING - ROOF DRAINS

Inspection Status - Approved

Date Description Inspector Results Comments
08/03/2006 PLUMBING - ROOF DRAINS Approved IVRS - Inspection :*
07/19/2006 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
1. INSTALL STRUT CLAMP OVERHEAD OUTSIDE LOBBY FOR ROOF DRAIN & OVERFLOW
2 OTHER ROOF DRAINS AND OVERFLOWS OK
07/17/2006 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
07/12/2006 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
WATER TEST RAIN DRAINS + OVERFLOW RAIN DRAINS THRU ROOF OK
1. PROVIDE RISER CLAMPS AT 2ND COVER, SUPPORT POPES IN WALL AND OVERHEAD CORRECTLY. PROVIDE GOOD UNDER DECK SUPPORT ON 3" RD + OFRD
PROVIDE REVISED APPROVED PLAN OF RAIN DRAINAGE.
05/30/2006 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
04/28/2006 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
2 - 4" OFRD EASTSIDE WATER TEST TO 4' (2) SETS 3" RD & OFRD WEST SIDE WATER TEST TO 4',
(1) 3" OFRD CENTER WEST WATER TEST TO 4'.
RAIN DRAIN PIPING TO BE TESTED THRU ROOF. NO PIPING SHALL BE DIRECTLY EMBEDDED IN CONCRETE OR GROUTED BLOCK COLL.
NOTE: SHEET MI.3 CALLS FOR 4" RD & OFRD AT CENTER WEST LOCATION.
03/21/2006 PLUMBING - ROOF DRAINS Partial Approval IVRS - Inspection :*
2-4" RD EASTSIDE WATER TEST STUB UP 5' + OUT 1' OK
1-3" RD STUBBED 5' UP + 1' OUT NORTHWEST OK
WHERE IS SOUTHWEST 3" RD?
03/20/2006 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*