Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05720
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINISH ELECTRIC |
|
| 03/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 03/01/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. FINISH BOX UNDER SERVER LINE 2. TIGHTEN LOOSE FITTING 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.2 4. KITCHEN RECEPTACLE TO BE GFCI AS PER 210.8 (B) 5. RECEPTACLES A MULTIWIRE CIRCUIT NEED BREAKER FOR THAT APPLICATION 210.4 6. CORDS NOT ALLOWED FOR PERMANENT WIRING METHODS 400.7 & 8 7. SECURE PUSH BUTTON TO WALL 8. WHRE IS EXIT LIGHT? 9. LIGHTS NOT ALL ARE WORKING 10. NIGHT LIGHTING NOT AS PER PLANS 11. WHERE IS REVISED FIXTURE SCHEDULE. |
|
| 11/16/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOND LIGHT POLES 250.148 & 250.54 OK CUBICLES AND OFFICES. 2. FINISH SERVER ROOM, KITCHEN |
|
| 11/13/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO OCCUPY NEED TEMP C OF O THROUGH STEVE LONG PRIOR TO USE |