Permit: T05CM05720

Parcel: 13316039A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05720

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/09/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
FINISH ELECTRIC
03/06/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
03/01/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. FINISH BOX UNDER SERVER LINE
2. TIGHTEN LOOSE FITTING
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.2
4. KITCHEN RECEPTACLE TO BE GFCI AS PER 210.8 (B)
5. RECEPTACLES A MULTIWIRE CIRCUIT NEED BREAKER FOR THAT APPLICATION 210.4
6. CORDS NOT ALLOWED FOR PERMANENT WIRING
METHODS 400.7 & 8
7. SECURE PUSH BUTTON TO WALL
8. WHRE IS EXIT LIGHT?
9. LIGHTS NOT ALL ARE WORKING
10. NIGHT LIGHTING NOT AS PER PLANS
11. WHERE IS REVISED FIXTURE SCHEDULE.
11/16/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOND LIGHT POLES 250.148 & 250.54
OK CUBICLES AND OFFICES.
2. FINISH SERVER ROOM, KITCHEN
11/13/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK TO OCCUPY NEED TEMP C OF O
THROUGH STEVE LONG PRIOR TO USE