Permit: T05CM05720

Parcel: 13316039A

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T05CM05720

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
02/23/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/14/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE KITCHEN
1. FINISH #6 PREVIOUS INSPECTION
01/31/2007 ELECTRIC - ABOVE CEILING Denied 1. IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE.
2. FINISH SUPPORT WIRES.
3. BOND DISCONNECT ENCLOSURE
4. TIGHTEN LOOSE FITTINGS
5. SUPPORT CONDUIT & M/C CABLES AS PER CODES.
6. MISSING COVER FOR JUNCTION BOXES
7. CHECK BOX FILL
8. VDV CABELING TO BE SUPPORTED 725.6
01/25/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK WALLS IN KITCHEN
OK BRIDGE
12/04/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
11/08/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) CONDENSOR PUMPS APPROVED BY STEVE LONG
2) OK TO TILE
11/07/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
11/06/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
10/17/2006 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FINISH CONDENSOR CIRCUIT
2) LABEL DISCONNECTS FOR A/C'S
3) SUPPORT FLEX ON VDV DROPS
4) SUPPORT CABLES AS THEY EXIT TRAY
5) CONDENSING PUMPS OK
6) SW BOARD MS OK
7) PANEL 1LA OK, AC1 OK, AC2 OK, 2LA OK
8) PANELS 1LA, 2LA NEED BUSHINGS AT FEEDER ENTRY (#4 AGW AND OVER) SLA OK
9) COMPUTER ROOM-3 CABLE TRAY BONDED TO PANEL ? OK
10) GAS AND WATER BONDS OK
11) A/C'S ON ROOF OK NEED LABELING
12) EXHAUST FAN ON ROOF TO BE MADE UP
13) NOTE TO GENERAL-POWER RELEASE IS FOR TESTING NOT FOR OCCUPANCY OR MOVING IN. NO OTHER ITEMS TO BE MOVED IN OR POWER CAN BE REMOVED
10/12/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK LIGHTS & CANS BOTH FLOORS.
1. CORD WILL NOT BE ALLOWED ABOVE CEILING 400.7 & 8
2. LABEL FAN COIL DISCONNECTS
3. NEED TO SEE POWER POLE CONNECTIONS.
4. SUPPORT VDV FLEX TO OFFICE FURNITURE
5. SUPPORT VDV CABELING UPON EXIT OF CABLE TRAY
09/12/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection 1. MANUFACTURERS CLIPS TO BE EFFECTIVE ALSO 2 ON ENDS
2. FINISH SUPPORT WIRES
3. FINISH VDV CABELING
08/31/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
1) FINISH UDV CABELING
2) FINISH WALLS
08/03/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CHECK BOX FILL
2. FILL UNUSED OPENINGS
3. FINISH VDV AS DISCUSSED
OK CANS OUTSIDE ENTRY
07/31/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SUPPORT VDV CABELING - CAMERA & SECURITY ALSO UPON EXITING OF CABLE TRAY
2. 2ND FLOOR CANS IN SOFFIT ROOM (CONFERENCE) SUPPORT MC CABLE

OK CANS STAIRWELL ENTRY 2ND FLOOR
OK BARRIER PAPER 2ND FLOOR MAIN AREA
07/26/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK FRONT SOFFIT CANS
06/22/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. VDV CABELING TO BE SUPPORTED AT 6' INTERVALS
OK CANS IN SOFFITS 1ST FLOOR
OK COLUMN WALLS AND WALL AT STAIRWELL AREA LOBBY.