Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM05720
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 02/14/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE KITCHEN 1. FINISH #6 PREVIOUS INSPECTION |
|
| 01/31/2007 | ELECTRIC - ABOVE CEILING | Denied | 1. IF MANUFACTURES CLIPS ARE USED THEY MUST BE EFFECTIVE. 2. FINISH SUPPORT WIRES. 3. BOND DISCONNECT ENCLOSURE 4. TIGHTEN LOOSE FITTINGS 5. SUPPORT CONDUIT & M/C CABLES AS PER CODES. 6. MISSING COVER FOR JUNCTION BOXES 7. CHECK BOX FILL 8. VDV CABELING TO BE SUPPORTED 725.6 |
|
| 01/25/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 12/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK WALLS IN KITCHEN OK BRIDGE |
|
| 12/04/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 11/08/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) CONDENSOR PUMPS APPROVED BY STEVE LONG 2) OK TO TILE |
|
| 11/07/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 11/06/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY CONTRACTOR |
|
| 10/17/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FINISH CONDENSOR CIRCUIT 2) LABEL DISCONNECTS FOR A/C'S 3) SUPPORT FLEX ON VDV DROPS 4) SUPPORT CABLES AS THEY EXIT TRAY 5) CONDENSING PUMPS OK 6) SW BOARD MS OK 7) PANEL 1LA OK, AC1 OK, AC2 OK, 2LA OK 8) PANELS 1LA, 2LA NEED BUSHINGS AT FEEDER ENTRY (#4 AGW AND OVER) SLA OK 9) COMPUTER ROOM-3 CABLE TRAY BONDED TO PANEL ? OK 10) GAS AND WATER BONDS OK 11) A/C'S ON ROOF OK NEED LABELING 12) EXHAUST FAN ON ROOF TO BE MADE UP 13) NOTE TO GENERAL-POWER RELEASE IS FOR TESTING NOT FOR OCCUPANCY OR MOVING IN. NO OTHER ITEMS TO BE MOVED IN OR POWER CAN BE REMOVED |
|
| 10/12/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK LIGHTS & CANS BOTH FLOORS. 1. CORD WILL NOT BE ALLOWED ABOVE CEILING 400.7 & 8 2. LABEL FAN COIL DISCONNECTS 3. NEED TO SEE POWER POLE CONNECTIONS. 4. SUPPORT VDV FLEX TO OFFICE FURNITURE 5. SUPPORT VDV CABELING UPON EXIT OF CABLE TRAY |
|
| 09/12/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | 1. MANUFACTURERS CLIPS TO BE EFFECTIVE ALSO 2 ON ENDS 2. FINISH SUPPORT WIRES 3. FINISH VDV CABELING |
|
| 08/31/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* 1) FINISH UDV CABELING 2) FINISH WALLS |
|
| 08/03/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CHECK BOX FILL 2. FILL UNUSED OPENINGS 3. FINISH VDV AS DISCUSSED OK CANS OUTSIDE ENTRY |
|
| 07/31/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SUPPORT VDV CABELING - CAMERA & SECURITY ALSO UPON EXITING OF CABLE TRAY 2. 2ND FLOOR CANS IN SOFFIT ROOM (CONFERENCE) SUPPORT MC CABLE OK CANS STAIRWELL ENTRY 2ND FLOOR OK BARRIER PAPER 2ND FLOOR MAIN AREA |
|
| 07/26/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK FRONT SOFFIT CANS |
|
| 06/22/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. VDV CABELING TO BE SUPPORTED AT 6' INTERVALS OK CANS IN SOFFITS 1ST FLOOR OK COLUMN WALLS AND WALL AT STAIRWELL AREA LOBBY. |