Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05CM05719
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* - GAUGE READING 10 PSI BUT NO AIR COMES OUT OF GAUGE - SUPPORT GAS PIPING FROM TRAILER NOT GROUND, USE APPROVED PIPE HANGERS - KEEP PIPING AT LEAST 6" ABOVE GROUND - REMOVED DAMAGED COPPER BRANCH LINE, USE SAME MATERIAL THROUGHOUT SYSTEM. - REMOVE GAS LINE TO FURNACE NOT BEING USED. - REMOVE TEE BRANCH BEHIND STOVE - CAP VALVE AT STOVE IF STOVE IS NOT INSTALLED. - PROVIDE STUDY SUPPORTING SUB-FLOOR UNDER WATER HEATER. - INSTALL WATER TIGHT DRAIN PAN W/DRAIN UNDER WATER HEATER - REPLACE T&P SAFETY VALVE AND GAS FLEX. |
|
| 01/06/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*ALL PIPING AND APPLIANCES WITHIN MH WILL HAVE TO MEET GAS CODE REQUREMENTS ALL PIPING WILL HAVE TO BE TESTED AGA VALVES REQUIRED BONDING OF GAS LINE REQUIRED FLUE PIPING WITHIN 10" OF COOLER WILL NEED TO BE EXTEND ?? 3' ABOVE COOLER BENT PIPING MUST BE REPLACED SUPPLY PIPING NEEDS TO BE SUPPORTED |
|
| 12/06/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled | ||
| 11/28/2005 | PLUMBING - GAS PRESSURE TEST | Cancelled |