Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOODS
Permit Number - T05CM05714
Inspection Description - MECHANICAL - HOODS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2007 | MECHANICAL - HOODS | Approved | IVRS - Inspection :* | |
01/03/2007 | MECHANICAL - HOODS | Partial Approval | IVRS - Inspection :* CHECKED FIRE WRAP OK TO COMPLETE HOOD INSTALLATION |
|
12/28/2006 | MECHANICAL - HOODS | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE ALL TAPE FROM JOINTS AND SEAMS TO CHECK FOR PROPER OVERLAP 2) BANDING IS NOT DONE CORRECTLY 3) WRAP MUST EXTEND TO BOTTOM OF DUCT AND UP TO TOP OF CURB 4) NEED ACCESS INTO ATTIC-CANNOT SEE ROOF PENETRATIONS 5) READ THE INSTALL INSTRUCTIONS FOR PROPER BAND SPACING AND OVERLAPPING |