Permit: T05CM05714

Parcel: 11105076B

Inspection Status: Approved

Inspection History: MECHANICAL - HOODS

Permit Number - T05CM05714

Inspection Description - MECHANICAL - HOODS

Inspection Status - Approved

Date Description Inspector Results Comments
01/17/2007 MECHANICAL - HOODS Approved IVRS - Inspection :*
01/03/2007 MECHANICAL - HOODS Partial Approval IVRS - Inspection :*
CHECKED FIRE WRAP OK TO COMPLETE HOOD INSTALLATION
12/28/2006 MECHANICAL - HOODS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE ALL TAPE FROM JOINTS AND SEAMS TO CHECK FOR PROPER OVERLAP
2) BANDING IS NOT DONE CORRECTLY
3) WRAP MUST EXTEND TO BOTTOM OF DUCT AND UP TO TOP OF CURB
4) NEED ACCESS INTO ATTIC-CANNOT SEE ROOF PENETRATIONS
5) READ THE INSTALL INSTRUCTIONS FOR PROPER BAND SPACING AND OVERLAPPING