Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE OK FOR SHEETROCK |
|
| 09/21/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* REMOVE STEEL NIPPLE FROM CONDENSATE & USE PLASTIC. SECONDARY DRAIN TO A CONSPICUOUS LOCATION. PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAINS. FRESH AIR NEEDS TO BE FILTERED. PROVIDE BACKING AROUND CEILING BOX. |