Permit: T05CM05714

Parcel: 11105076B

Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T05CM05714

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
CORRECTIONS HAVE BEEN MADE
OK FOR SHEETROCK
09/21/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
REMOVE STEEL NIPPLE FROM CONDENSATE & USE PLASTIC.
SECONDARY DRAIN TO A CONSPICUOUS LOCATION.
PROVIDE MIN. 1/8" PER FT. SLOPE ON DRAINS.
FRESH AIR NEEDS TO BE FILTERED.
PROVIDE BACKING AROUND CEILING BOX.