Permit: T05CM05714

Parcel: 11105076B

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T05CM05714

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
02/15/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
09/27/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECEPTION TOILET RM OK TO COVER
09/22/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
- WC AND DF OK TO COVER,
CLEANOUT AT LAVITORY IS NOT.
- SEC. 707.7 REQUIRES CLEANOUT EXTENSIONS TO BE MADE W/WYE PATTERN FITTINGS. IT IS ACCEPTABLE TO INSTALL & SWEEP ON YOUR TEST WYE AND CAP IMPROPER CLEAN OUT.
- HAVE PLUMBER READ APPRENTICE SERIES LITERATURE LEFT W/INSPECTION.
09/21/2006 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
- MAKE CLEANOUT AT WC ACCESSIBLE.
- USE PURPLE PRIMER ON PVC PIPE & FITTINGS.
- PROVIDE TEST THROUGH ROOF.

- AT LAV, WYE PATTERN FITTINGS ARE REQUIRED FOR CLEAN OUT EXTENSIONS. INSTALL TEST WYE AT BASE OF STACK. HAVE SOLVENT WELD CAP ON SITE TO CAP WYE AFTER TEST.
- SILICONE IS NOT AN APPROVED THREAD SEALANT.
- NOTE: CLEAN OUT PLUGS USED TO RECEIVE SCREW FROM COVER SHALL HAVE A FACTORY TAP.