Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T05CM05714
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* RECEPTION TOILET RM OK TO COVER |
|
09/22/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WC AND DF OK TO COVER, CLEANOUT AT LAVITORY IS NOT. - SEC. 707.7 REQUIRES CLEANOUT EXTENSIONS TO BE MADE W/WYE PATTERN FITTINGS. IT IS ACCEPTABLE TO INSTALL & SWEEP ON YOUR TEST WYE AND CAP IMPROPER CLEAN OUT. - HAVE PLUMBER READ APPRENTICE SERIES LITERATURE LEFT W/INSPECTION. |
|
09/21/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* - MAKE CLEANOUT AT WC ACCESSIBLE. - USE PURPLE PRIMER ON PVC PIPE & FITTINGS. - PROVIDE TEST THROUGH ROOF. - AT LAV, WYE PATTERN FITTINGS ARE REQUIRED FOR CLEAN OUT EXTENSIONS. INSTALL TEST WYE AT BASE OF STACK. HAVE SOLVENT WELD CAP ON SITE TO CAP WYE AFTER TEST. - SILICONE IS NOT AN APPROVED THREAD SEALANT. - NOTE: CLEAN OUT PLUGS USED TO RECEIVE SCREW FROM COVER SHALL HAVE A FACTORY TAP. |