Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM05714
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/20/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY - 2099 OUTDOOR LIGHTING FINAL 1. SERVICE RACEWAY BOND IS UNDERSIZED - NEC 250.102C FROM PREVIOUS CORRECTION 2. METER STILL SEALED 3. ON ROOF, HAVE EQUIPMENT OPEN FOR INSPECTION (COOLER, EX. MOTOR) SECURE RACEWAYS TO STRUCTURE NOTCH IN USE COVER. 4. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED HAVE ELECTRICIAN TO BE ON SITE FOR INSPECTION TO PROVIDE ACCESS. |
|
02/15/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY, WILL INSPECT ROOFTOP AND REST OF INTERIOR NEXT TRIP PREVIOUS CORRECTIONS ONGOING 1. EXIT LIGHTS NOT WORKING 2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4 3. ALL CKT CONDUCTORS, INCLUDING EQUIPMENT GROUND TO BE RAN IN SAME RACEWAY - NEC 250.134 B 4. EMERGENCY LIGHT (EGRESS EXTERIOR) NOT INSTALLED 5. HOOD AND MAKE UP AIR TO BE INTERLOCKED! |
|
02/12/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PARTIAL INSPECTION FOR EXTERIOR AT SERVICE ONLY-NO INTERIOR INSPECTION AT THIS TIME 2) AT EXTERIOR PANEL BOARD: SERVICE CONDUCTORS ARC OVER-FUSED NEC 310 3) BOND SERVICE RACEWAY NEC 250.92 & 250.102 C 4) IDENTIFY SERVICE DISCONNECT NEC 230.7 B 5) SHEATHING FOR WIRING TO ENTER PANEL MINIMUM 1/4", CLOSE OFF OPENINGS NEC 312.5 6) PROPERLY IDENTIFY EQUIPMENT GROUNDS NEC 250.119 7) OPEN METER FOR INSPECTION 8) CHECK FOR CORRECT CKT PHASING-NEC 100 9) MAKE SURE PANEL DIRECTORY CORRECT NEC 408.4 |