Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05714

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
02/20/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY - 2099 OUTDOOR LIGHTING FINAL

1. SERVICE RACEWAY BOND IS UNDERSIZED - NEC 250.102C
FROM PREVIOUS CORRECTION
2. METER STILL SEALED
3. ON ROOF, HAVE EQUIPMENT OPEN FOR INSPECTION (COOLER, EX. MOTOR) SECURE RACEWAYS TO STRUCTURE NOTCH IN USE COVER.
4. PANEL DIRECTORY TO BE CORRECTLY IDENTIFIED
HAVE ELECTRICIAN TO BE ON SITE FOR INSPECTION TO PROVIDE ACCESS.
02/15/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY, WILL INSPECT ROOFTOP AND REST OF INTERIOR NEXT TRIP

PREVIOUS CORRECTIONS ONGOING

1. EXIT LIGHTS NOT WORKING
2. PANEL DIRECTORY NOT CORRECTLY IDENTIFIED -- NEC 408.4
3. ALL CKT CONDUCTORS, INCLUDING EQUIPMENT GROUND TO BE RAN IN SAME RACEWAY - NEC 250.134 B
4. EMERGENCY LIGHT (EGRESS EXTERIOR) NOT INSTALLED
5. HOOD AND MAKE UP AIR TO BE INTERLOCKED!
02/12/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PARTIAL INSPECTION FOR EXTERIOR AT SERVICE ONLY-NO INTERIOR INSPECTION AT THIS TIME
2) AT EXTERIOR PANEL BOARD: SERVICE CONDUCTORS ARC OVER-FUSED NEC 310
3) BOND SERVICE RACEWAY NEC 250.92 & 250.102 C
4) IDENTIFY SERVICE DISCONNECT NEC 230.7 B
5) SHEATHING FOR WIRING TO ENTER PANEL MINIMUM 1/4", CLOSE OFF OPENINGS NEC 312.5
6) PROPERLY IDENTIFY EQUIPMENT GROUNDS NEC 250.119
7) OPEN METER FOR INSPECTION
8) CHECK FOR CORRECT CKT PHASING-NEC 100
9) MAKE SURE PANEL DIRECTORY CORRECT NEC 408.4