Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T05CM05714
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/28/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK BATHROOM & COUNTER WALLS |
|
09/27/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 9:50 AM NOT READY |
|
09/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* - STILL HAVE WIRING IN BATHROOM - OK COVER EXCEPT SOUTH BATH WALL. |
|
09/21/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SEAL UNUSED OPENING IN EQUIPMENT 2. 90 DEG. MC FITTINGS NOT ALLOWED IN CONCEALED WALLS/SPACES. 3. REMOVE UNUSED/TEMPORARY CONDUCTORS FROM AREAS TO BE COVERED. 4. REMOVE USUSED WIRE. |