Permit: T05CM05712

Parcel: 116094110


Addresses:

2960 W SALVIA DR

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
07/06/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
07/03/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ENGINEER APPROVED COMPACTION RESULTS
2) REBAR TO BE MINIMUM 3" FROM FORMS AND DIRT
3) VERTICAL REBAR FROM RETAINER TO BE BENT HORIZONTALLY AND TIED INTO SLAB
4) TOE DOWNS WITH REBAR MISSING
5) FOOTINGS NOT DEEP ENOUGH SEE PLAN
6) REBRA HORIZONTALLY MISSING THROUGHOUT SLAB
7) STOPPED INSPECTION
06/19/2006 EXCAVATION/LAYOUT REBAR & ZON Cancelled IVRS - RI canceled
05/02/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
04/28/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) RETAINER FROM S.W. CORNER BEDROOM TO S.W. CORNER GARAGE APPROX 23'-6 1/2"
04/27/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) EAST WALL GARAGE RETAINER INCOMPLETE
02/15/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) LOWER LEVEL OK TO POUR
02/14/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT MATCH VERTICAL REBAR FOR REAR WALL WITH ANY SECTIONS SHOWN
2) WAS RETAINING WALL WITH LOCKING BLOCKS APPROVED ?
3) NO UFER
4) INSTALL ALL P.A.'S PER MANUFACTURERS INSTRUCTIONS TO PREVENT SPAWING
02/10/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*