Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* EXTERIOR LIGHTING 1. THE EQUIPMENT GROUND IS UNDERSIZED - NEC 250.122 B 2. GROUND ALL J-BOXES -- NEC 250.148 3. MISSING POLE J-BOX COVER -- NEC 110.12A 4. SERVICE DISCONNECT TO BE ACCESSIBLE - NOT LOCKED NEC 230.70 5. ORIGINAL HARDWARE TO BE REINSTALLED ON PANEL AND TEP LOCK REMOVED -- NEC 110.3B 6. NEED CORD FOR DISPOSAL 7. EMERGENCY LIGHTING NOT WORKING, NOT PER PLAN AND ALSO NEEDS TO COMPLY WITH NEC 700.12 E 8. PANEL DIRECTORIES NOT CORRECTLY IDENTIFIED - NEC 408.4 9. BOXES TO BE FLUSH FOR COMBUSTIBLE SURFACE - NEC 314.20 (DO NOT CUT EXTENDERS - NEC 110.3B) 10. RECEPTACLES AND COVERS TO SIT AGAINST WALL NEC 406.4 11. BOND CLAMP FOR PHONE GROUND UNDERSIZED -- NEC 110.3B |