Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T05CM05694
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/01/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
04/20/2006 | BUILDING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) DOG IN YARD-NO ACCESS |
|
03/24/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDUIT CONNECTORS AND COUPLINGS MUST BE OF RAIN TIGHT TYPE, NOT SET SCREW WHERE THEY ARE NOT UNDER ROOF. WEST SIDE 2) HOT AND NEUTRAL REVERSED ON OUTLETS AT BBQ |