Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
Permit Number - T05CM05692
Inspection Description - PLUMBING - ROUGH, SOIL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 04/10/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES FROM 3/31/06 |
|
| 03/31/2006 | PLUMBING - ROUGH, SOIL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT LOCATE GRAY WATER PLANS ON APPROVED PLANS 2) INSTALL 2 WAY CLEANOUT OUTSIDE HOUSE WALL LINE 3) MUST HAVE 12" DIRT COVER OVER SEWER LINE OUTSIDE HOUSE 4) DRAINAGE PIPING APPEARS TO HAVE INADEQUETE FALL 5) STOPPED INSPECTION 6) MUST VERIFY FLOOR ELEVATION WITH UPSTREAM MAN HOLE TO DETERMINE NEED FOR BACKWATER VALVE. CHECK WITH YOUR LICENSED PLUMBER IF BWV REQUIRED UPPER FLOW PLUMBING TO TIE IN DOWN STREAM OF BWV |