Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/23/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GFI PROTECTED OUTLETS REQUIRED IN GARAGE 2) EXTERIOR OUTLET CAN NOT SHARE KITCHEN CIRCUIT 3) SEDIMENT TRAP NEEDED ON GAS LINE AT FURNACE AND WATER HTR 4) CAP GAS LINE AT DRYER 5) INSTALL DBL WALL FLUE ELBOW AT WATER HTR 6) TO MAINTAIN 6" CLEARANCE FOR SINGLE WALL 7) INSTALL RANGE 8) BOND GAS PIPE 9) MAX FUSE 50 AMP IN A/C DISCONNECT |