Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05CM05692

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
02/22/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/23/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GFI PROTECTED OUTLETS REQUIRED IN GARAGE
2) EXTERIOR OUTLET CAN NOT SHARE KITCHEN CIRCUIT
3) SEDIMENT TRAP NEEDED ON GAS LINE AT FURNACE AND WATER HTR
4) CAP GAS LINE AT DRYER
5) INSTALL DBL WALL FLUE ELBOW AT WATER HTR
6) TO MAINTAIN 6" CLEARANCE FOR SINGLE WALL
7) INSTALL RANGE
8) BOND GAS PIPE
9) MAX FUSE 50 AMP IN A/C DISCONNECT