Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T05CM05692
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
| 04/10/2006 | EXCAVATION/LAYOUT REBAR & ZON | Partial Approval | IVRS - Inspection :* 1) EXTERIOR FTGS OK TO POUR |
|
| 03/08/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) FOUNDATION DETAIL PAGE 5 (FTG STEM DETAIL) REQUIRES FOOTINGS TO BEAR MINIMUM 18" BELOW NATURAL GRADE, CONCRETE 12" WITH 3-#5 HORIZONTAL REBAR AND #5 REBAR VERTICAL 48 SPACING NEED TO SET PROPERTY PINS, PULL STRING LINES TO CHECK SET BACKS BE SURE TO SET GRADE STAKES-PINS TO VERIFY DEPTH OF FOOTINGS 2) OBTAIN SOILS ENGINEER REPORT FOR SOILS TESTING AT BEARING FOUNDATIONS FROM CERTIFIED ENGINEER (I WAS RIGHT AROUND THE CORNER SO i CAME AND DID THE INSPECTION-DID NOT CALL FIRST) |
|
| 01/18/2006 | EXCAVATION/LAYOUT REBAR & ZON | Not ready for Inspection | IVRS - Inspection :* 1) FOOTING BOTTOMS COVERED WITH FIST SIZED STONES, AD IS TYPICAL FOR ENTIRE LOT 2) RETAIN SOILS ENGINEER TO PROVIDE PARTICULAR FOUNDATION PLAN FOR THIS LOT |