Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T05CM05692

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
04/10/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1) EXTERIOR FTGS OK TO POUR
03/08/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) FOUNDATION DETAIL PAGE 5 (FTG STEM DETAIL) REQUIRES FOOTINGS TO BEAR MINIMUM 18" BELOW NATURAL GRADE, CONCRETE 12" WITH 3-#5 HORIZONTAL REBAR AND #5 REBAR VERTICAL 48 SPACING NEED TO SET PROPERTY PINS, PULL STRING LINES TO CHECK SET BACKS BE SURE TO SET GRADE STAKES-PINS TO VERIFY DEPTH OF FOOTINGS
2) OBTAIN SOILS ENGINEER REPORT FOR SOILS TESTING AT BEARING FOUNDATIONS FROM CERTIFIED ENGINEER (I WAS RIGHT AROUND THE CORNER SO i CAME AND DID THE INSPECTION-DID NOT CALL FIRST)
01/18/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
1) FOOTING BOTTOMS COVERED WITH FIST SIZED STONES, AD IS TYPICAL FOR ENTIRE LOT
2) RETAIN SOILS ENGINEER TO PROVIDE PARTICULAR FOUNDATION PLAN FOR THIS LOT