Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2005 | PLUMBING - INTERMEDIATE | Approved | SOIL WATER TEST IS OK WATER DISTRIBUTION IS OK OK FOR DRY WALL |
|
| 11/30/2005 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SHALL PROVIDE A C.O @ VERTICAL RISER FOR KITCHEN SINK CANNOT REDUCE THE TRAP ARM FROM 2" TO 1 1/2 FOR KITCHEN SINK. IF YOU USE A 2" TRAP ARM THEN A 2" A 1/2" TRAP ARM FROM THE BARREL TO THE P-TRAP. SHALL LOCATE HORIZONTAL VENT 6" ABOVE FLOOD RIM LEVEL OR PROVIDE 45 DEGREE. SHALL PROVIDE A WATER TEST ON NEW PIPEING TO TOP OF VENT. OK TO DRY WALL ALL OTHER AREAS |