Permit: T05CM05677

Parcel: 133426050

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/14/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/07/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. NEED A GROUND PATH FOR SUB-PANEL
2. TERMINATE ALL STRANDS OF CONDUCTORS
3. FINISH PREVIOUS ITEMS 2 & 3
04/05/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. SWITCHES TO BE GROUNDED
2. BOXES TO BE FLUSH AT COMBUSTIBLES AND NO MORE THAN 1/4" AT NON COMBUSTIBLES 314.20
3. SEPARATE GROUNDING AND GROUNDED CONDUCTORS.
4. CLEAN EXCESS DIRT OUT OF PANEL.
5. ONLY ONE CONDUCTOR TERMINATION TO A LUG.
6. USE ANTIOXID COMPOUND ON ALL ALUMINUM CONDUCTORS.