Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/07/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. NEED A GROUND PATH FOR SUB-PANEL 2. TERMINATE ALL STRANDS OF CONDUCTORS 3. FINISH PREVIOUS ITEMS 2 & 3 |
|
| 04/05/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. SWITCHES TO BE GROUNDED 2. BOXES TO BE FLUSH AT COMBUSTIBLES AND NO MORE THAN 1/4" AT NON COMBUSTIBLES 314.20 3. SEPARATE GROUNDING AND GROUNDED CONDUCTORS. 4. CLEAN EXCESS DIRT OUT OF PANEL. 5. ONLY ONE CONDUCTOR TERMINATION TO A LUG. 6. USE ANTIOXID COMPOUND ON ALL ALUMINUM CONDUCTORS. |