Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/02/2005 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :*OK ROUGH | |
| 11/30/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*FINISH PREVIOUS ITEMS AT PANEL. OK TO ROCK EXC?? AS NOTED OK ONE SIDE ONLY AT PANEL |
|
| 11/28/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999*SUPPORT NM CABLE AS PER CODE ALSO S? CABLES. PROTECT CABLES AT STUDS & JOIST SUPPORT NM CABLES ABOVE PANEL CABLES TO BE SECURED TO PANEL AS PER 312.5 TIGHTEN LOOSE CLAMPS WE HAVE CONDUCTOR OVER FILL AT BOXES EXTENDER WILL BE NEEDED TO BRING BOXES FLUSH WITH FACE OF DRY WALL HAVE BUILDING INSPECTOR DETERMINE IF HOLES IN CENTER OF JOIST ARE ALLOWED. |