Permit: T05CM05674


Addresses:

1100 S RANDOLPH WY


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T05CM05674

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/02/2006 BUILDING - FINAL Approved IVRS - Inspection :*
02/28/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NOT ABLE TO VERIFY PEDESTAL REINFORCEMENT WORK COVERED & NO CAV FOR INSPECTIONS. PICTURES DOWNLOADED ON COMPUTER INDICATE THAT #3 TIES WERE PLACED IN @ INSIDE OF VERTICAL REBAR IN LIEN OF OUTSIDE
2. NEED STAMPED LETTER FROM ENGINEER OF RECORD INDICATING SIZE & AMOUNT OF THROUGH BOLTS @ BEAM SEATS FOR GLU-LAM BEAMS & DECISION FOR MISPLACED TIES @ PEDESTALS.
3. NEED WELDER'S CERTS. FOR ANY FIELD WELDING & SHOP CERTS. FOR WELDING FOR ANY WELDING DONE @ SHOP NOT ABLE TO VERIFY WELDS OR DRY PAUSING OF GROUT @ COLUMN BASES.