Permit: T05CM05653

Parcel: 13316024M

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/03/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/28/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON-COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20
2. CLEAN TRASH OUT OF FLOOR BOXES.
3. FINSIH COUNTER WIRING.
4. EM LIGHTING AND EXIT LIGHTS TO BE ON CIRCUIT SERVING AREA 700.12
5. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8
6. LIGHTING TRANSFORMER - PLEASE VERIFY LISTING
7. PLEASE VERIFY LISTING FOR CORD & PLUG CONNECTION INSTA HOT UNITS.
8. DISCONNECTING MEAN NOT ALLOWED ON AN ACCESSIBLE PANEL 440.14
9. COLOR CODE PHASE CONDUCTORS AT DISCONNECT (A/C)
10. FILL UNUSED OPENING.
11. WE HAVE A 2ND DISCONNECT AT A/C NOT SHOWN ON PLANS PLEASE PROVIDE A LETTER FOR THIS CHANGE.