Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/03/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE AT NON-COMBUSTIBLES NEED AN APPROVED EXTENDER RING 314.20 2. CLEAN TRASH OUT OF FLOOR BOXES. 3. FINSIH COUNTER WIRING. 4. EM LIGHTING AND EXIT LIGHTS TO BE ON CIRCUIT SERVING AREA 700.12 5. CORDS NOT ALLOWED ABOVE CEILING 400.7 & 8 6. LIGHTING TRANSFORMER - PLEASE VERIFY LISTING 7. PLEASE VERIFY LISTING FOR CORD & PLUG CONNECTION INSTA HOT UNITS. 8. DISCONNECTING MEAN NOT ALLOWED ON AN ACCESSIBLE PANEL 440.14 9. COLOR CODE PHASE CONDUCTORS AT DISCONNECT (A/C) 10. FILL UNUSED OPENING. 11. WE HAVE A 2ND DISCONNECT AT A/C NOT SHOWN ON PLANS PLEASE PROVIDE A LETTER FOR THIS CHANGE. |