Permit: T05CM05653

Parcel: 13316024M

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/20/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS
01/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK FRONT SOFFIT
OK WALLS ROOM 100-102
01/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK WALLS ROOM #104, 106, 109-115 AND DEMISING WALL
01/09/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*SUPPORT VDV CABLEING AS PER 725.6
SUPPORT BOXES IN WALLS.
SUPPORT M/C CABLE WITHIN 12" OF BOXES AND 6'
FINISH INSTALLATION PLASTER RINGS
DO NOT BUNDLE M/C CABLES
FILL UNUSED OPENINGS -NOT AN EMPTY FITTING
12/15/2005 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK U.G AS NOTED
OK 7 FLOOR BOXES FOR FLOOR RECEPTACLES W/3/4" CONDUIT