Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/20/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK WALLS |
|
| 01/18/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK FRONT SOFFIT OK WALLS ROOM 100-102 |
|
| 01/12/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK WALLS ROOM #104, 106, 109-115 AND DEMISING WALL |
|
| 01/09/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :*SUPPORT VDV CABLEING AS PER 725.6 SUPPORT BOXES IN WALLS. SUPPORT M/C CABLE WITHIN 12" OF BOXES AND 6' FINISH INSTALLATION PLASTER RINGS DO NOT BUNDLE M/C CABLES FILL UNUSED OPENINGS -NOT AN EMPTY FITTING |
|
| 12/15/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK U.G AS NOTED OK 7 FLOOR BOXES FOR FLOOR RECEPTACLES W/3/4" CONDUIT |