Inspection History Details
Permit: T05CM05640
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/30/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BACKFLOW CERTIFICATION ON SITE 2. MAKE ALL CLEANOUTS ACCESSIBLE. REMOVE TEST PLUGS USE COUNTER SINK, TAPPED, PLUGS (LEAVE OPEN) 3. INSTALL CHECK VALVE ON RE-CIRC LINE |
|
| 03/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE CALL IN AND HAVE APPROVED ALL REQUIRED INSPECTIONS PRIOR TO CALLING FINAL. NOTE: THIS OFFICE DOES NOT SUPPLY A PUNCH LIST FOR THE PLUMBER. 2. ABOVE CEILING COVERED WITHOUT INSPECTION. 3. WHEN THE INSPECTOR WROTE:"HANGERS AT EACH CHANGE OF DIRECTION OR ELEVATION" - THAT MEANT EACH SIDE. 4. HOT NOT INSULATED AS DIRECED ON 2/28/06 |