Inspection History Details
Permit: T05CM05640
Inspection Status: Not ready for Inspection
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/02/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLUMBER: ALL PIPING REQUIRE SUPPORT AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES - THEN NO MORE THAN SO MANY FEET ACCORDING TO TABLE 3-1 94 UPC |
|
| 03/02/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV WATER TEST OK YARD WATER PIPING OK SUPPORT HORIZONTAL ABS AT 4' AND AT CHANGES OF DIRECTION. PROVIDE MIDSPAN SUPPORTS ON VERTICAL VENTS ABOVE MEZZANINE. PROVIDE ABS PERM CAP AT CAPPED FIXTURE OK TO INSULATE HOT & HWR |
|
| 02/15/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1 1/2 PVC 1120 SCH 40 330 PSI -- DWV -- FROM METER TO WITHIN 15' OF BUILDING W/TYPEL COPPER SERVICE AND OVERHEAD TO RESTROOMS. 60 + PSI TEST 1 1/2 COPPER REQUIRES SUPPORT AT 6' NORTH/SOUTH RUN OK EAST/WEST SECTION OF OVERHEAD NEEDS MORE HANGERS PROVIDE LISTING FOR PVC REPLACEMENT OF RPA WILL REQUIRE A TUCSON WATER PERMIT |