Permit: T05CM05640

Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
03/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PLUMBER: ALL PIPING REQUIRE SUPPORT AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES - THEN NO MORE THAN SO MANY FEET ACCORDING TO TABLE 3-1 94 UPC
03/02/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
02/28/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
DWV WATER TEST OK
YARD WATER PIPING OK
SUPPORT HORIZONTAL ABS AT 4' AND AT CHANGES OF DIRECTION.
PROVIDE MIDSPAN SUPPORTS ON VERTICAL VENTS ABOVE MEZZANINE.
PROVIDE ABS PERM CAP AT CAPPED FIXTURE
OK TO INSULATE HOT & HWR
02/15/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1 1/2 PVC 1120 SCH 40 330 PSI -- DWV -- FROM METER TO WITHIN 15' OF BUILDING W/TYPEL COPPER SERVICE AND OVERHEAD TO RESTROOMS.
60 + PSI TEST
1 1/2 COPPER REQUIRES SUPPORT AT 6' NORTH/SOUTH RUN OK
EAST/WEST SECTION OF OVERHEAD NEEDS MORE HANGERS
PROVIDE LISTING FOR PVC
REPLACEMENT OF RPA WILL REQUIRE A TUCSON WATER PERMIT