Permit: T05CM05640

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/29/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/28/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED A TWO POLE BREAKER FOR MULTI-WIRE BRANCH CKT ON SAME YOKE - NEC 210.7 (C)
2. IDENTIFY BRANCH CKTS IN PANELS NEC 408.4
3. IDENTIFY RTU'S