Permit: T05CM05640
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/28/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED A TWO POLE BREAKER FOR MULTI-WIRE BRANCH CKT ON SAME YOKE - NEC 210.7 (C) 2. IDENTIFY BRANCH CKTS IN PANELS NEC 408.4 3. IDENTIFY RTU'S |