Inspection History Details
Permit: T05CM05640
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | ELECTRIC - ABOVE CEILING | Approved | PER EL FINAL | |
| 03/24/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. TWO BOXES IN BREAKROOM CEILING ARE OVERFILLED INSTALL EXTENSION BOXES AS NEEDED NEC 314.16 OK TO COVER CEILING IN BREAKROOM AFTER CORRECTION MADE |