Permit: T05CM05640

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
03/29/2006 ELECTRIC - INTERMEDIATE Approved PER EL FINAL
03/24/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
03/17/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) STILL NEED TO IDENTIFY ALL SERVICE DISCONNECTS
2) INSTALL BUSHINGS FOR ALL CONDUCTORS #4 AND LARGER
3) PROVIDE TORQUE LETTER
4) THIS IS A SERVICE INSPECTION ONLY
03/16/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The service is not per code.| 210*
1. PROVIDE PROPER SIZE BOND CONDUCTOR FOR SERVICE RACEWAYS - 2002 NEC 250.102 (C)
2. ARRANGE SERVICE RACEWAY BOND CONDUCTORS TO ELIMINATE OBJECTIONABLE CURRENT NEC 250.6
3. CONDUCTORS IN GEAR NOT TO PASS THROUGH OTHER SECTIONS NEC 408.3 (AX3)
4. TIGHTEN ALL GROUNDING BUSHING AND LUG SET SCREWS NEC 250.4
5. INSTALL FUSES AND MAKE UP SUBPANEL FEEDERS
6. PROVIDE LETTER OF TORQUE FOR EQUIPMENT NEC 110.3 (B)
7. IDENTIFY ALL SERVICE DISCONNECTS NEC
03/15/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1 PM SER SWITCH GEAR NOT SET IN PLACE YET
02/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BREAKROOM, OK RESTROOMS, SHOWROOM RECEPT. EAST OF RESTROOM
WATER HEATER & SPARE J-BOX
02/15/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TO COVER SECONDARY DITCH
2) NOTE: PROVIDE CONCRETE ENCASEMENT BY TRANSFORMER ALSO, PROVIDE 2 GROUND RODS WITH A #4 CU GROUNDING ELECTRODE CONDUCTOR FOR NEW SERVICE ALSO, VERIFY BLDG STEEL AND METAL & PIPE SYSTEM IS BONDED
01/27/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*OK 2 FLOOR BOXES
OK ACCESS TO EXISTING OPENING NORTH WALLS
01/26/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
MARK 260-1168 300-20?
1. PROVIDE ACCESS FOR EXISTING WIRING
2. SUPPORT LOOSE BOXES AS NEEDED