Inspection History Details
Permit: T05CM05640
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/29/2006 | ELECTRIC - INTERMEDIATE | Approved | PER EL FINAL | |
| 03/24/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 03/17/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) STILL NEED TO IDENTIFY ALL SERVICE DISCONNECTS 2) INSTALL BUSHINGS FOR ALL CONDUCTORS #4 AND LARGER 3) PROVIDE TORQUE LETTER 4) THIS IS A SERVICE INSPECTION ONLY |
|
| 03/16/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. PROVIDE PROPER SIZE BOND CONDUCTOR FOR SERVICE RACEWAYS - 2002 NEC 250.102 (C) 2. ARRANGE SERVICE RACEWAY BOND CONDUCTORS TO ELIMINATE OBJECTIONABLE CURRENT NEC 250.6 3. CONDUCTORS IN GEAR NOT TO PASS THROUGH OTHER SECTIONS NEC 408.3 (AX3) 4. TIGHTEN ALL GROUNDING BUSHING AND LUG SET SCREWS NEC 250.4 5. INSTALL FUSES AND MAKE UP SUBPANEL FEEDERS 6. PROVIDE LETTER OF TORQUE FOR EQUIPMENT NEC 110.3 (B) 7. IDENTIFY ALL SERVICE DISCONNECTS NEC |
|
| 03/15/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1 PM SER SWITCH GEAR NOT SET IN PLACE YET |
|
| 02/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* BREAKROOM, OK RESTROOMS, SHOWROOM RECEPT. EAST OF RESTROOM WATER HEATER & SPARE J-BOX |
|
| 02/15/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK TO COVER SECONDARY DITCH 2) NOTE: PROVIDE CONCRETE ENCASEMENT BY TRANSFORMER ALSO, PROVIDE 2 GROUND RODS WITH A #4 CU GROUNDING ELECTRODE CONDUCTOR FOR NEW SERVICE ALSO, VERIFY BLDG STEEL AND METAL & PIPE SYSTEM IS BONDED |
|
| 01/27/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :*OK 2 FLOOR BOXES OK ACCESS TO EXISTING OPENING NORTH WALLS |
|
| 01/26/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* MARK 260-1168 300-20? 1. PROVIDE ACCESS FOR EXISTING WIRING 2. SUPPORT LOOSE BOXES AS NEEDED |