Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/30/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. CORRECTIONS MADE OK 2. OK TO COVER ALL AREAS |
|
| 03/17/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. A TRAP ARM MAY NOT CHANGE SIZE TRAP AND TRAP ARM TO BE THE SAME SIZE TRAP MAY BE ONLY ONE PIPE SIZE LARGER THAN THE TAILPIECE OF THE FIXTURE. A LAVATORY HAS A 1 1/4" TAILPIECE. 2. SUPPORT VERTICAL ABS |
|
| 03/17/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PLEASE RE-READ MY CORRECTIONS FROM 3/16/06 LAVATORY TAIL PIECE = 1 1/4" PLUS ONE PIPE SIZE = 1 1/2" 1 1/2" IS THE SIZE OF THE ENTIRE TRAP ARM AND THE TRAP 1 1/2" TRAP ARM MAY NOT EXCEED THREE FEET SIX INCHES FROM TRAP WEIR TO POINT OF VENT. |