Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2006 | ELECTRIC - TEMPORARY SERVICE | Approved | IVRS - Inspection :* | |
| 05/15/2006 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CHARLIE OK PWOER BEFORE 1. RETIGHTEN 1ST GROUND ROD CLAMP. 2. INSTALL 100 AMP. BREAKERS AT MAINS 3. INSIDE PANEL CALLS FOR 3 ARC FAULT BREAKERS. 4. CONDUCTORS IN PANEL LEFT UNTERMINATED TO BE LANDED ON BREAKER, AND GROUNDS TERMINATED. 5. ALL INSIDE WIRING IF NOT FINISHED TO BE PROPERLY DEAD ENDED OR WIRE NUTTED OF - MAY BECOME ENERGIZED. 6. NEED TO GET AN APPROVAL FROM CHARLIE ON INTERMEDIATE PRIOR TO TEMP. POWER. |