Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/19/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/28/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL |
|
| 03/24/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED NAIL PLATES WHERE LESS THAN 1 1/4" FROM STUD FACE. 2. ROMEX OUTSIDE WALL FOR BEDROOM SWITCH 3. HOOD NOT ALLOWED ON COUNTER OUTLET CKT. 4. PRINT SHOWS UNDERGROUND SERVICE FEED? 5. METAL BOXES NEED GROUND SCREW TIGHTENED. 6. LOW VOLTAGE WIRE IN CEILINGS NOT SECURED/SUPPORTED |
|
| 03/20/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. NEED NAIL PLATES IN SEVERAL AREAS 2. PROPERLY GROUND ALL METAL BOXES 3. DISPOSAL SWITCH BOX OVERFILLED 4. DON'T STAPLE ROMEX ON ITS SIDE 5. SERVICE SIZE AND TYPE HAS VARIED FROM PLAN AND HAS NO GROUNDING ELECTRODE. 6. PROPERLY SECURE AND SUPPORT ALL LOW VOLTAGE WIRING |