Permit: T05CM05637

Parcel: 10603070D


Addresses:

3235 N STONE AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/25/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/19/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL
03/24/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED NAIL PLATES WHERE LESS THAN 1 1/4" FROM STUD FACE.
2. ROMEX OUTSIDE WALL FOR BEDROOM SWITCH
3. HOOD NOT ALLOWED ON COUNTER OUTLET CKT.
4. PRINT SHOWS UNDERGROUND SERVICE FEED?
5. METAL BOXES NEED GROUND SCREW TIGHTENED.
6. LOW VOLTAGE WIRE IN CEILINGS NOT SECURED/SUPPORTED
03/20/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. NEED NAIL PLATES IN SEVERAL AREAS
2. PROPERLY GROUND ALL METAL BOXES
3. DISPOSAL SWITCH BOX OVERFILLED
4. DON'T STAPLE ROMEX ON ITS SIDE
5. SERVICE SIZE AND TYPE HAS VARIED FROM PLAN AND HAS NO GROUNDING ELECTRODE.
6. PROPERLY SECURE AND SUPPORT ALL LOW VOLTAGE WIRING