Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/23/2006 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 10/13/2006 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) H20 HEATER PTR LINE TO EXIT TO EXTERIOR 2) INSTALL TRAP A/C CONDENSATE 3) NO LOCATION KITCHEN COUNTER TOP WALL LINE TO BE MORE THAN 24" FROM RECEPTACLE LEFT OF SINK 4) CAULK BASE OF TOILET 5) BREAK OFF SMALL BOLT-ANTI SIPHON HOSE BIBS 6) A/C DISCONNECT FUSES FADED-INSTALL 2 NEW 20 AMP FUSES PER LISTING 7) POST ADDRESS NUMBERS ON HOUSE FRONT 8) PUT DISHWASHER INTO CABINETS 9) BACKFILL H20 LINE TRENCH, SLOPE GRADING AWAY FROM HOUSE THROUGHOUT 10) REMOVE WOOD FORMS AWAY FROM FOUNDATION 11) INSTALL RANGE ANTI TIP DEVICE 12) STOPPED INSPECTION-INCOMPLETE |