Permit: T05CM05607

Parcel: 115154840

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/12/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
07/11/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 4 OF 5 VERTICALS FELL INTO HOLES, MUST PUT LONGER VERT. REBAR IN TO OVERLAP REBAR FROM 48" LIFT AND TO ? TO TOP OF FINISHED WALL ABOVE BOND BEAM
REMOVE ALL PAPER AND MORTAR FROM HOLES TO BE GROUTED SO AS TO ALLOW GROUT TO GO TO 48" LEVEL
STOPPED INSPECTION
REFEE DUE
07/07/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
MUST INSTALL VERTICAL REBAR IN BLOCK
MINIMUM 15" OVERLAP
VERT. REBAR MUST CARRY TO TOP OF WALL.
07/06/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INSTALL VERTICAL REBAR IN BLOCK
2) NEED LADDER TO INSPECT
06/26/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
1) 1ST 48" LIFT