Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T05CM05606
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/28/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* 1) PAPERWORK FROM ENGINEER SENT RECORDS 2) ITEM 03050 NOT REQUIRED-ALL ELECTRIC |
|
02/09/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) PENDING NOTE #3 FROM INSPECTION DATED 2/7/06-OK TO WRAP HOUSE |
|
02/07/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) BLOCKS MISSING BETWEEN TRUSSES AT HIGH CEILING 2) WIND BRACES MISSING NAILS 3) REPAIR FOR 12/DT-1 MUST BE APPROVED BY CITY OF TUCSON DSD BEFORE INTERMEDIATES |
|
02/01/2006 | EXT METAL CLIPS/EXT SHEATHING | Cancelled | CANCELLED PER TRAVIS OF STANDARD PACIFIC #240-8413 | |
01/31/2006 | EXT METAL CLIPS/EXT SHEATHING | Cancelled | CANCELLED PER TRAVIS OF STANDARD PACIFIC #240-8413 | |
01/30/2006 | EXT METAL CLIPS/EXT SHEATHING | Cancelled | CANCELLED PER TRAVIS OF STANDARD PACIFIC #240-8413 | |
01/27/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 12DT1 NOT PER PLAN, PROVIDE DETAIL AS BUILT APPROVED 2) MTS48 STRAPS MISSING AT S.E. CORNER AND AT DECK N.E. 3) 7 BLOCKS MISSING BETWEEN TRUSSES |