Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/13/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - SENSING TUBES ON DUCT SMOKE DETECTORS NOT LONG ENOUGH. - PROVIDE INSTALL INSTRUCTIONS - WATER HEATER VENT TERMINATION NOT TO CODE - PROVIDE VIBRATION ISOLATORS - AIR BALANCE OK |
|
| 07/23/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PROVIDE A SECONDARY DRAIN ON ALL FAN COILS - DUCT SMOKE DETECTORS TO BE INSTALLED IN RETURN DUCTS. - WATER HEATER VENT CANNOT TERMINATE INTO A WEATHER HOOD. - NEED TO TEST DUCT SMOKE DETECTOR - FAN COILS ARE LEAKING WATER. CAP OFF UNUSED OUTLETS - PERMANENTLY I.D ALL EQUIPMENT - PROVIDE EQUIPMENT ISOLATORS |