Permit: T05CM05596

Parcel: 125050530


Addresses:

700 N WILSON AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/24/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CHECK LIST CALL WHEN ALL COMPLETE
08/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. NEED PROPER WORKING CLEARANCE @ DISCONNECT
FOR FC-3 IN ACTIVITY ROOM.
2. LIBRARY FINAL OK
08/13/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION ONLY
1. PLANS TO BE REVISED TO SHOW ACTUAL SCOPE OF WORK
2. PROVIDE GFI PROTECTION FOR ALL 120V SINGLE
PHASE 15/20 AMP RECEPTACLES IN KITCHEN - NEC 210.8 B3
3. LABEL PANEL DIRECTORIES PROVIDED WITH PANELS AND BE CORRECT -- NEC 408.4
4. PROVIDE DISCONNECTING MEANS FOR APPLIANCES
NEC 422.32
5. J-BOX FOR DISPOSAL IS OVERFILLED, UNGROUNDED, NEED PROPER CONNECTOR FOR CORD - -NEC 314.16, 400, 250
6. NEED BUSHING FOR CONDUCTORS IN PVC - NEC 352.46
7. 4.P.4 NEEDS PROPER FRONT CLEARANCE FOR DISCONNECT
NEC 110.26
8. IN AC FEEDER J-BOXES REMOVE PAINT BEHIND LUGS, SHEET METAL SCREWS NOT ALLOWED FOR GROUNDS, SPLIT BOLTS TO MANY CONDUCTORS -- NEC 110.3B, 250.8, 110