Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/24/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CHECK LIST CALL WHEN ALL COMPLETE |
|
| 08/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. NEED PROPER WORKING CLEARANCE @ DISCONNECT FOR FC-3 IN ACTIVITY ROOM. 2. LIBRARY FINAL OK |
|
| 08/13/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. PLANS TO BE REVISED TO SHOW ACTUAL SCOPE OF WORK 2. PROVIDE GFI PROTECTION FOR ALL 120V SINGLE PHASE 15/20 AMP RECEPTACLES IN KITCHEN - NEC 210.8 B3 3. LABEL PANEL DIRECTORIES PROVIDED WITH PANELS AND BE CORRECT -- NEC 408.4 4. PROVIDE DISCONNECTING MEANS FOR APPLIANCES NEC 422.32 5. J-BOX FOR DISPOSAL IS OVERFILLED, UNGROUNDED, NEED PROPER CONNECTOR FOR CORD - -NEC 314.16, 400, 250 6. NEED BUSHING FOR CONDUCTORS IN PVC - NEC 352.46 7. 4.P.4 NEEDS PROPER FRONT CLEARANCE FOR DISCONNECT NEC 110.26 8. IN AC FEEDER J-BOXES REMOVE PAINT BEHIND LUGS, SHEET METAL SCREWS NOT ALLOWED FOR GROUNDS, SPLIT BOLTS TO MANY CONDUCTORS -- NEC 110.3B, 250.8, 110 |