Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/24/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
08/10/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) OK CEILING TILES KITCHEN
2) CLARIFY INTERLOCK FOR HOODS, NOT PER PLAN
08/06/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR KITCHEN CEILING
1. FOR WALK-INS STRAP FLEX, GROUND BOXES, SEAL INTERIOR OF RACEWAYS
2. USE THE EQUIPMENT GROUND TO GROUND ALL J-BOXES EQUIP. - NEC 250.148
3. KITCHEN HOOD LIGHTS NOT WIRED, MAKE UP AIR TO BE ENERGIZED AT SAME TIME EX. FAN IS ENERGIZED.
4. PROPERLY SUPPORT LOW VOLTAGE WIRING
5. STRAP LOOSE EMT
6. IDENTIFY HOOD DISCONNECTS
02/07/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/31/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*