Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/10/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK CEILING TILES KITCHEN 2) CLARIFY INTERLOCK FOR HOODS, NOT PER PLAN |
|
| 08/06/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR KITCHEN CEILING 1. FOR WALK-INS STRAP FLEX, GROUND BOXES, SEAL INTERIOR OF RACEWAYS 2. USE THE EQUIPMENT GROUND TO GROUND ALL J-BOXES EQUIP. - NEC 250.148 3. KITCHEN HOOD LIGHTS NOT WIRED, MAKE UP AIR TO BE ENERGIZED AT SAME TIME EX. FAN IS ENERGIZED. 4. PROPERLY SUPPORT LOW VOLTAGE WIRING 5. STRAP LOOSE EMT 6. IDENTIFY HOOD DISCONNECTS |
|
| 02/07/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 01/31/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |