Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/14/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM #5 NOT COMPLIED WITH |
|
| 03/08/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GARAGE CS 20 STRAPS CANNOT BE ? AROUND NAILER 2) SHORT RADIUS 90 CANNOT BE AT BOTTOM OF DWV STACK 3) HORIZONTAL DWV DRAIN MUST HAVE 1/4" PER FT PITCH 4) RED HEAD ANCHOR BOLTS 5) MAXIMUM ALLOWED STAIR RISE DIFFERENCE 3/8" NOW 7 1/8 TO 7 7/8 6) SEWER VENT MUST BE 10 FEET FROM AIR INTAKE 7) NO SECOND FLOOR DWV WATER TEST 8) NAIL PROTECT WIRES WITHIN 1 1/4" OF STUD SURFACES 9) PLUMBING LEAK 10) ANCHOR BOLTS MISSING THROUGHOUT 11) PLUMBING OUT OF WALL |
|
| 03/06/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) SEPERATE/BLCOKD COMBUSTION AIR 2) NO DWV WATER TEST 3) NO POTABLE WATER TEST 4) NO GAS PRESSURE TEST 5) STOPPED INSPECTION |