Permit: T05CM05592

Parcel: 140377820

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/30/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
03/24/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*
03/23/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) GLB IN GARAGE REQUIRES 4-2 X 4 POSTS
2) 7/SD3 NOT COMPLIED WITH AT GARAGE
3) GARAGE HEADER NOT CLIPPED
4) 1/SD2 RIBBON MUST EXTEND TO DBL TOP PLATES
5) CS 20 STRAPS MISSING SOUTH WALL AND NORTH WALL
03/22/2006 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection IVRS - Inspection :*