Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/17/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Second floor girder post cut at garage southwest corner (repeat) Fire stop floors (repeat) Fire stop bedroom chase (repeat) No second floor DWV water test (repeat) You must pay a reinspection fee within 5 days No yellow inspection card |
|
| 03/16/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 1, 2, 3, 4, 7, 8 AND 10 FROM 3/10/06 NOT DONE |
|
| 03/10/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RED HEAD ANCHOR BOLTS LOOSE 2) OSB SHEAR NOT NAILED 3) 2ND FLOOR GIRDER POST CUT BY WATER HEATER 4) FIRE STOP FLOORS 5) NAIL TRIMMED 6) ANCHOR BEARING WALLS 7) PROVIDE 22 X 48 OVER ? ACCESS 8) NAIL FIRE STOP 9) FIRE STOP DUCT 10) NO 2ND FLOOR DWV TEST 11) SUPPORT CONDENSATE 12) SUPPORT HORIZONTAL DWV |
|
| 03/08/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) LATH NOT COMPLETE 2) RED HEAD ANCHOR BOLTS LOOSE 3) SECURE WIRES AT 4' ON CENTER-BELOW CEILING 4) GARAGE SHEARWALL NOT NAILED PER PLAN 5) SUPPORT 3/4" GAS LINE AT 8' ON CENTER 6) SHORT RADIUS 90 NOT ALLOWED AT BOTTOM OF DWV STACK 7) HORIZONTAL DWV DRAIN MUST HAVE 1/4" PER FT PITCH 8) HOLDOWN MISSING 9) STOPPED INSPECTION-TOO MANY ITEMS |