Permit: T05CM05586

Parcel: 140377760

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/22/2006 FRAMING Approved IVRS - Inspection :*
03/17/2006 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Second floor girder post cut at garage southwest corner (repeat)
Fire stop floors (repeat)
Fire stop bedroom chase (repeat)
No second floor DWV water test (repeat)
You must pay a reinspection fee within 5 days
No yellow inspection card
03/16/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 1, 2, 3, 4, 7, 8 AND 10 FROM 3/10/06 NOT DONE
03/10/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) RED HEAD ANCHOR BOLTS LOOSE
2) OSB SHEAR NOT NAILED
3) 2ND FLOOR GIRDER POST CUT BY WATER HEATER
4) FIRE STOP FLOORS
5) NAIL TRIMMED
6) ANCHOR BEARING WALLS
7) PROVIDE 22 X 48 OVER ? ACCESS
8) NAIL FIRE STOP
9) FIRE STOP DUCT
10) NO 2ND FLOOR DWV TEST
11) SUPPORT CONDENSATE
12) SUPPORT HORIZONTAL DWV
03/08/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) LATH NOT COMPLETE
2) RED HEAD ANCHOR BOLTS LOOSE
3) SECURE WIRES AT 4' ON CENTER-BELOW CEILING
4) GARAGE SHEARWALL NOT NAILED PER PLAN
5) SUPPORT 3/4" GAS LINE AT 8' ON CENTER
6) SHORT RADIUS 90 NOT ALLOWED AT BOTTOM OF DWV STACK
7) HORIZONTAL DWV DRAIN MUST HAVE 1/4" PER FT PITCH
8) HOLDOWN MISSING
9) STOPPED INSPECTION-TOO MANY ITEMS