Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/24/2006 | FRAMING | Approved | IVRS - Inspection :* | |
| 03/22/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ANCHOR BOLTS NOT INSTALLED AT 16" ON CENTER GARAGE SOUTHWEST 2) NAIL END OF SHEARWALL AT 3'-0" 3) INADEQUATE HEAD ROOM AT STAIRS 4) B-VENT REQUIRES OFF SET MAX 60 DEGREE FROM VERTICAL 5) ELECTRIC BOXES MUST BE 1/4" BELOW DRYWALL 6) BEARING STUDS CUT 7) DWV TEST OK |
|
| 03/21/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* | |
| 03/17/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) NO DWV WATER TEST 2) SEAL FLOOR PENETRATIONS 3) FIRE STOP CHASE AT STAIR 4) 12" CLEARANCE REQUIRED AT CAN LIGHTS TO PES 5) 1/2" CLEARANCE REQUIRED AT KITCHEN SINK CAN LIGHT AND DUCT RESTRICTED 6) ANCHOR BOLTS REQUIRED AT 16" ON CENTER GARAGE SHEARWALL 7) STOPPED INSPECTION-TOO MANY ITEMS |
|
| 03/16/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) ANCHOR BOLTS MISSING IN GARAGE 2) GARAGE CS 20 STRAPS MISSING AND NOT NAILED 3) SEAL FLOOR PENETRATIONS 4) NAIL PROTECT PLUMBING 5) HOLDOWNS MISSING NUTS 6) NO DWV WATER TEST 7) ANCHOR LAUNDRY BOX 8) FIRE STOP CHASES 9) STOPPED INSPECTION-TOO MANY ITEMS |