Permit: T05CM05585

Parcel: 140377780

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
03/24/2006 FRAMING Approved IVRS - Inspection :*
03/22/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ANCHOR BOLTS NOT INSTALLED AT 16" ON CENTER GARAGE SOUTHWEST
2) NAIL END OF SHEARWALL AT 3'-0"
3) INADEQUATE HEAD ROOM AT STAIRS
4) B-VENT REQUIRES OFF SET MAX 60 DEGREE FROM VERTICAL
5) ELECTRIC BOXES MUST BE 1/4" BELOW DRYWALL
6) BEARING STUDS CUT
7) DWV TEST OK
03/21/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
03/17/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) NO DWV WATER TEST
2) SEAL FLOOR PENETRATIONS
3) FIRE STOP CHASE AT STAIR
4) 12" CLEARANCE REQUIRED AT CAN LIGHTS TO PES
5) 1/2" CLEARANCE REQUIRED AT KITCHEN SINK CAN LIGHT AND DUCT RESTRICTED
6) ANCHOR BOLTS REQUIRED AT 16" ON CENTER GARAGE SHEARWALL
7) STOPPED INSPECTION-TOO MANY ITEMS
03/16/2006 FRAMING Denied IVRS - Inspection :
Work is not complete enough to inspect.| 950*
1) ANCHOR BOLTS MISSING IN GARAGE
2) GARAGE CS 20 STRAPS MISSING AND NOT NAILED
3) SEAL FLOOR PENETRATIONS
4) NAIL PROTECT PLUMBING
5) HOLDOWNS MISSING NUTS
6) NO DWV WATER TEST
7) ANCHOR LAUNDRY BOX
8) FIRE STOP CHASES
9) STOPPED INSPECTION-TOO MANY ITEMS