Permit: T05CM05578

Parcel: 140377750

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/23/2006 BUILDING - FINAL Approved IVRS - Inspection :*
05/22/2006 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 4" CLEARANCE REQUIRED BETWEEN WEEP SCREED AND SOIL
2) A/C CONDENSOR PLATFORM MUST BE 3" ABOVE GRADE
3) A/C CONDENSOR DISCONNECT ACCESS BLOCKED BY UNIT MUST HAVE 30" X 30" CLEARANCE
05/19/2006 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
1) NOT READY-CANCELLED PER CONTRACTOR