Permit: T05CM05574

Parcel: 140373780


Addresses:

7083 S PLOVER CT

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
03/29/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
03/28/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) DAMAGE CABLE SHEATHING NOT REPAIRED
2) 1" CLEARANCE REQUIRED BETWEEN CABLE ENDS AND FORMS
3) UFER CLAMP LOOSE ON REBAR
4) GROUND CONDUCTOR LOOSE ON CLAMP