Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALLED PER REDLINED CHANGES ON PLAN FINAL APPROVAL UPON PLAN REVISION. |
|
| 05/16/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* PREVIOUS CORRECTIONS NOT MADE. MET W/ERNESTO (PLUMBER). YOUR PLAN CLEARLY SPECIFIES THAT: 1. TYPE L COPPER TUBE IS TO BE USED FOR DOMESTIC WATER PIPING. 2. WATER SERVICE ENTERS BUILDING ON WEST END NOT ON SOUTHSIDE. 3. BUILDING DRAIN IS 4". PIPING INSTALLATIONS ARE NOT PER PLAN. YOU WERE MADE AWARE OF THIS ON FEBRUARY 2ND IF YOU WISH TO INSTALL PIPING IN A MANNER OTHER THAN SPECIFIED ON PLAN. YOU NEED TO REVISE PLAN ACCORDINGLY. PLAN SPECS SUPERCEDE UPC MIN. STANDARDS |
|
| 05/12/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CLEAN OUT EXTENSIONS SHALL BE WYE BRANCH FITTINGS. VTR SHALL BE 3" CLEAN OUT ABOVE LAV WILL INTERFERE WITH MIRROR. HORIZONTAL CHANGES OF DIRECTION ON TRAP ARM SHALL BE MADE WITH THE USE OF WYE PATTERN FITTINGS. CLOSET FLANGE SHALL BE FASTENED TO FLOOR. WH REQUIRES A DRAIN PAN AND DRAIN. PLAN CALLS FOR WATER PIPING TO BE TYPE L COPPER. PEX HAS BEEN INSTALLED PEX NOT INSTALLED PER CODE. |
|
| 03/15/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE CORRECTIONS FROM YESTERDAYS INSPECTION HAVE NOT BEEN MADE 3" SEWER INCREASES TO 4" AT APPROX. 10 FT FROM BUILDING 1. A FULL SIZED CLEANOUT IS REQUIRED AT THIS LOCATION 2. PROVIDE A TEST ON SEWER PIPING. DO NOT USE WATER FROM AN UNPROTECTED SUPPLY! IMMEDIATELY INSTALL A HOSE BIBB VAC BREAKER ON TEMPORARY HOSE BIBB |
|
| 03/14/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CARDS HCS, WATER LINE 631-4045 03040 - YARD WATER LINE AND 03055 PLUMBING SEWER ARE NOT ON INSPECTION CARD BECAUSE THE PLAN INDICATES THAT THESE ARE EXISTING. WATER PIPING PLAN DOES NOT SHOW BACKFLOW SERVICE PROTECTION. OK TO COVER 1" PVC YARD WATER LINE. I WILL NEED TO SEE THE RP INSTALLATION AT A LATER TIME. REVISE PRINT TO SHOW BACKFLOW PREVENTION ASSEMBLY AND LOCATION OF WATER LINE. INSTALL A HOSE BIB VACUUM BREAKER ON TEMPORARY CONSTRUCTION HB BUILDING SEWER REQUIRES A TEST. DO NOT COVER. PROVIDE A 4" CLEANOUT FOR SEWER. |