Permit: T05CM05565

Parcel: 124161510


Addresses:

1013 S TYNDALL AV

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
07/24/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
03/31/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
03/30/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
4" BUILDING SEWER, 4" CLEAN OUTS OK TO COVER
WAITING FOR PLAN REVISION OF 3" BUILDING DRAIN TO APPEAR
ROUGH SOIL INSPECTION
02/09/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
3" ABS DRAIN FROM TOILET RM & LOUNGE THROUGH EXTERIOR CLEAN OUTS W/WATER TEST ON ONE RISER OK
PEX WATER PIPING LOOPED UNDER SLAB TO LOUNGE OK
PLAN MUST BE REVISED TO SHOW ACCURATE PIPE SIZING AND REFLECT CHANGE OF WATER PIPING PLAN REVISION WILL BE REQUIRED FOR FINAL APPROVAL.
02/08/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
3" ABS BUILDING DRAIN IS IN VIOLATION OF UPC SEC 708 THERE ARE AT LEAST 4 PLACES W/LESS THAN 1/4' PER FOOT SLOPE & CORRECTIONS REQUIRED FROM THE PREVIOUS TWO INSPECTIONS HAVE NOT BEEN COMPLETED.
A REINSPECTION FEE IS BEING ASSESSED
FEE MUST BE PAID WITHIN 5 DAYS OR NO FURTHER INSPECTIONS WILL BE PERFORMED.
02/06/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*CORRECTIONS FROM PREVIOUS INSPECTION HAVE NOT BEEN MADE
3" DRAIN PIPING REQUIRES A MIN OF 2 % FALL THERE APPEARS TO BE ADEQUATE FALL AVAILABLE. THE UPPER TERMINAL COULD BE RAISED IF NECESSARY
THE PLAN CLEARLY SHOWS A 4" BUILDING DRAIN, IF THIS IS GOING TO BE REVISED. RED LINE. PRINT TO COINSIDE WITH INSTALLATION
CALL FOR INSPECTION AFTER CORRECTIONS HAVE BEEN MADE. CARLOS INFORMED ME THAT HE IS GOING TO SUE THE CITY
02/02/2006 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL PER PLAN OR REVISE PLAN SEE P101 4" SANITARY
2. PROVIDE 2% FALL IN ALL AREAS