Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/24/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ADDRESS SERVICE 2. 4/0 COPPER - 230 AMPS ONLY PLAN CALLS FOR 400 A 3. SEAL HOLE BACK OF SERVICE 4. MBJ FROM UFER TO NEUTRAL BAR TO BE #2 5. DOUBLE LUGGING ON UFER TO BE CORRECTED 6. CHECK WITH TED ON RISER EXTENSION BEFORE ANY CHANGES ON O/H DROP. |
|
| 07/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SEE NOTES 5/12/06 FOR SERVICE CORRECTIONS WILL NEED REVISION FOR SERVICE MODIFICATIONS. 2. ALSO NOTE THAT WALLS COVERED PRIOR TO ROUGH IN OR INTERMEDIATE APPROVAL, UFER INSP. NOT APPROVED. |