Permit: T05CM05565

Parcel: 124161510


Addresses:

1013 S TYNDALL AV

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/25/2006 ELECTRIC - INTERMEDIATE Approved
05/23/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER GUTTER IN OFFICE #1
05/18/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SEE NOTES #3 ALSO BOND J-BOX
2. SUPPORT 3/4" EMT WITHIN 3' OF BOX, TIGHTEN FITTINGS.
05/12/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
NOTES:
1. WAIVER WILL BE REQUIRED FOR OVERHEAD SERVICE - PLAN CALLS FOR U.G FED SERVICE.
2. MC CABLES MUST TERMINATE WITH APPROVED MC CONNECTORS INTO PANEL. BUNDLING CABLES THRU NIPPLE NOT ALLOWED.
3. SUPPORT MC WITHIN 12' OF TERMINATION.
4. INSTALL MAIN BONDING JUMPER BETWEEN GROUNDING ELECTRODE CONDUCTOR & NEUTRAL IN PANEL.