Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/01/2006 | MECHANICAL - FINAL | Partial Approval | 1. TIGHTEN ALL THERMOSTAT CONNECTORS ON ROOF. 2. GREASE COLLECTION RECEPTACLE ON EXHAUST BLOWER. 3. TAPE REFRIG. LINES ON WALK-IN CONDENSER TOGETHER. |
|
| 06/27/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CHECK R.A. UNDER STAGE. OK TO COVER 2) COMBUSTION AIR TO WATER HEATER OK 3) VENT ON WATER HEATER OK 4) STAINLESS STEEL MUST BE BEHIND HOOD AND 18" IN ALL DIRECTIONS 5) INSULATE MAKE UP AIR DUCT OR PROVIDE LETTER FROM ENGINEER 6) OK TO FILE FOR TEMP C OF O |
|
| 06/23/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* TERMINATE DRYER VENT AS PER PLANS. CHECKED WELDS ON GREASE DUCT & CHECKED FIRE WRAP. OK TO PROCEED WITH HOOD. |
|
| 06/22/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DISCUSSED ELEVATED STAGE RETURN PLENUM. MAKE NECESSARY CORRECTIONS AS NOTED BY ENGINEER. USE STEEL DUCT FOR COMBUSTION AIR AS NOTED. |
|
| 06/20/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ELEVATED STAGE AREA. RETURN PLENIUM. 1. CANNOT HAVE COMBUSTIBLES MUST HAVE FLAME/SMOKE RATING ETC. IMC SEC. 602.2.1 2. TYPE I HOOD, DUCT, ETC. STARTING 3. COMBUSTION AIR DUCTS - AT WATER HTR. RM., NEED TO BE OF GALV. STEEL. IMC SEC. 708.1 |