Permit: T05CM05562

Parcel: 12112044B


Addresses:

5225 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
08/11/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
08/02/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE FLO CONTROL FOR GREASE TRAP & VENT
2. EXPOSE LISTING PLATES FOR GAS APPLIANCES IN KITCHEN
3. PROVIDE CORRECT COUPLING FOR 2-COMP SINK DRAIN IN WATER HEATER ROOM.
4. SECURE EXPANSION TANK AT WATER HEATER
5. PROVIDE CORRECT BACKFLOW PROTECTION FOR GUNS AT BAR FOR WATER SUPPLY.
6. MAKE WATER TIGHT ALL FIXTURES
06/27/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CALL FOR AND GET APPROVED ALL INSPECTIONS NOT YET APPROVED 03035, 03036, 03040, 03050 AND 03052. PROVIDE INSPECTION HISTORY
ICE MAKER NOT INSTALLED, BACKFLOW NOT INSTALLED
KITCHEN SINKS AND EQUIPMENT NOT YET INSTALLED-ROOM 102
NO CLEANOUT AT WASHER OUTLET BOX
WATER HEATER LOCATION CHANGE SHALL BE REFLECTED ON PLAN REVISION
3" PIPE PENETRATING ROOF REQUIRES A FLASHING CHANGE OF GAS PIPING REQUIRES PLAN REVISION
INSTALL VALVE AHEAD OF ? VALVE