Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE FLO CONTROL FOR GREASE TRAP & VENT 2. EXPOSE LISTING PLATES FOR GAS APPLIANCES IN KITCHEN 3. PROVIDE CORRECT COUPLING FOR 2-COMP SINK DRAIN IN WATER HEATER ROOM. 4. SECURE EXPANSION TANK AT WATER HEATER 5. PROVIDE CORRECT BACKFLOW PROTECTION FOR GUNS AT BAR FOR WATER SUPPLY. 6. MAKE WATER TIGHT ALL FIXTURES |
|
| 06/27/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CALL FOR AND GET APPROVED ALL INSPECTIONS NOT YET APPROVED 03035, 03036, 03040, 03050 AND 03052. PROVIDE INSPECTION HISTORY ICE MAKER NOT INSTALLED, BACKFLOW NOT INSTALLED KITCHEN SINKS AND EQUIPMENT NOT YET INSTALLED-ROOM 102 NO CLEANOUT AT WASHER OUTLET BOX WATER HEATER LOCATION CHANGE SHALL BE REFLECTED ON PLAN REVISION 3" PIPE PENETRATING ROOF REQUIRES A FLASHING CHANGE OF GAS PIPING REQUIRES PLAN REVISION INSTALL VALVE AHEAD OF ? VALVE |